Wednesday, March 10, 2010

Proper wire Ampacity

Proper wire Ampacity, and choosing the correct wire size for a particular installation seems to be an area many of us get rusty on. calculating correct wire Ampacity is a critical step in order to protect and provide for proper branch circuit loads and feeder requirements.
Table 310.16 is too confusing! I hear this a lot. As an electrical instructor for Texas Electrician Exams, I teach many journeymen, masters, even city inspectors hot to study for, and successfully pass their Texas electrical PSI provided test. It is my opinion that wire sizing for correct amperage is the single largest areas of confusion. to be fair, the 2008 National Electrical Code added an additional step to the Ampacity de-rating requirements. I have even seen recent nationally publishes articles that have incorrectly applied these new de-rating factors. So don’t feel bad if you have some confusion, you’ve got lost of company!
There is some hope with the new edition of the 2011 NEC in it’s proposed format. A new layout for T310.16 is probably going to happen, and hopefully this new layout will make it an easier table to utilize.
I always instruct my students to mark step I through Step IV in their code books. Step I is the top chart on page 147. We begin (always) with what I like to call our “core” Ampacity. For example, a 350 THHN cu conductor under the 75 degree column is 310 Amperes. This is the core value that we will perform all subsequent steps on.
The biggest question I get, by far, is “What is the 90 degree column for, and how/when can I use it?” Well, it’s simple really, you must have three (3) separate items (rules) in order to utilize that column as your beginning core value AND your final calculation must answer TRUE to one additional item. The 3 caveats are:

Rule I. There must be de-rating factors to consider.
Rule II. The insulation of the conductor must be rated for the 90 degree column (and not limited by any specific code article to a lower temperature).
Rule III. The installation must be a dry or damp location for the conductors.

True or false: The final adjusted must NOT be larger than that Ampacity value under the 75 column.

Under Rule I, we must have an ambient temperature adjustment, roof-top temperature adjustment, or a number of current carrying conductor adjustment. If none of those apply then the 90 degree is off limit. Any one of these adjustments factors alone or together with others, would be enough to allow for the 90 degree as a starting point.
Under Rule II, this initially seems to be a given, however, a closer look at certain insulation ratings in their various respective sections in Chapter 3, and T310.13, restrict certain type and certain installations to a lower temperature rating. (Examples: 336.26 (NMS) restricts the cable assembly to the 60 degree column- even though it requires the individual conductors to be rated at 90 degrees; Types XHHW, XHH, THHW, and RHH(among others) are all limited by T310.13 to 75 degrees column when installed in a WET location.)
Under Rule III, we acknowledge the previous examples and use caution when installing in a wet location. Most 90 degrees rated insulation types are restricted to 75 degrees in wet locations. Further, new code rules for 2008 classify ALL interiors of raceways, where directly exposed to weather or buried below grade, are classified as wet locations.
Finally, our calculated core Ampacity-after adjustments for any applicable de-rating factors-must not exceed the value for the same size wire under the 75 degree column. So to answer the 90 degree column question: hardly ever used.
Back to our 350 kcmil cu conductor Ampacity calculation. Step I we found the core Ampacity to be 310A under the 75 degree column (let’s assume a roof top installation: therefore a “wet location”). Next we examine our two ambient temperature steps. Under the main amperage chart on page 147, we see C degrees and F degrees de-rating factors. Notice 26-30 degree C and 78-86 degree F are equal to 1.00 or (100%). This is because the table is based on 86 degrees F initially. Temperatures greater (hotter) than 86 degrees F or (30 degrees C) must be de-rated. (Heat causes resistance-resistance in turn causes more heat, with a potential of a thermal run-away effect). These values are multipliers. A 106 degrees F installation would have a factor of .82 (or 82%). Thus our 310 Amps would be de-rated at 310AX.82=254.2 Amps. Flipping back one page (146) we see the new rooftop temperature adder table. If exposed to sun-light on a roof top, we have to increase our ambient temperatures PRIOR to choosing our multiplier.
The table in listed by heights (in inches) above the roof top surface. (The closer to the surface- greater convection of heat transfer occurs due to the reflected heat). At 3” above we would increase our 106 degree F by an amount of 30 degree F. Therefore we actually have a 136 degree F installation. That ambient temperature has a factor of .58 (or 58%). Thus our 310A core Ampacity is=310AX.58=179.8A (or 180 Amps) A very significant Ampacity de-rating!
Finally we must count our current carrying conductors under T310.15(b)(2)(a) for more than 3 current carrying conductors. Always keep in mind that neutrals can sometimes be considered a C.C.C. and might push a 3 phase service into this de-rating table.
That’s it. Pretty simple-yes? If anyone has further questions, comments, suggestions, or wants more practice, contact us via email and we will be glad to help.

Thanks for Reading,

Mitchell S Tolbert
1-888-473-1826
Contact@ElectricianTesting.com
www.ElectricianTesting.com

13 comments:

  1. Hi I'm Haley, a Texas Electrician Continuing Education student. This blog really is a real big help in my studies. Thanks for the info. More power!

    ReplyDelete
  2. This is great information for installing in damp locations. Too many people don't take the moisture in the area into account when wiring. I'll have to keep this information handy to pass along.

    Richard | http://nepeanelectric.com

    ReplyDelete
  3. Really informative blog thanks for sharing. To hire electrician sloughcontact us!!

    ReplyDelete
  4. If any of your appliances aren’t working after plugging in then the outlet is totally damaged. For this, you can check the outlet using any tool and can also determine the working of your appliance. If your appliance is working then your outlet is damaged. For this, you will need to find on the internet for the best electrician services in Reading me and get the repair and replacement done.

    ReplyDelete
  5. Nice Post!
    Faulty circuits, loose wiring, and more can lead to fires and various dangerous hassles. Here, finding yourself a reputable, reliable, and affordable electrician in Slough is vital as only they can save you from any damage and provide the quality electrical assistance you need.

    ReplyDelete
  6. Electrical hassles are very common yet daunting - be it at a commercial place or at your residence. Every homeowner or business owner is always concerned about electrical safety as such mishaps not only lead to damage of belongings but the loss of life as well.

    The safety of electrical works is a necessity but what if any mishap occurs. How would you deal with any electrical damage at your place? Obviously, you can rely on your own DIYs, and hiring the professional electrician in Reading comes as the right solution.

    Wondering why not fix the hassles on your own? Here below are shared some interesting reasons why to hire skilled pros only and how they can be beneficial in this job. Let’s get started then.

    ReplyDelete
  7. Pertaining to residential home use, electrical contractors are usually needed to re-wire or perhaps maintain present systems. They're also needed for building construction, including upgrades and remodels, to place all the electric outlets and lighting. Calgary electrician

    ReplyDelete
  8. Nice Post!
    The safety of electrical works is a necessity but what if any mishap occurs. How would you deal with any electrical damage at your place? Obviously, you can rely on your own DIYs, and hiring the professional electrician in Slough comes as the right solution.
    Complex electric hassles can be quite hard to fix. This means it can take enough time to get you back on track. However, top-notch professionals can help in saving this time by solving the hassle effectively and in no time.

    ReplyDelete
  9. It is always required to leave the electrical repairs and installation job on the professionals. Faulty circuits, loose wiring, and more can lead to fires and various dangerous hassles. Here, finding yourself a reputable, reliable, and affordable electrician in Reading is vital as only they can save you from any damage and provide the quality electrical assistance you need. However, before taking any decision, considering shared below factors is necessary. All these factors can help in better decision making and get the right electrical assistance without any damage to your and your belongings.

    ReplyDelete
  10. The blog was absolutely fantastic! Lot of information is helpful in some or the other way. Keep updating the blog, looking forward for more content...Great job, keep it up.
    Electrician in Islamabad

    ReplyDelete

  11. Do you need electrician services? Muscat home is a leading company which

    provides skilled professional who inspects, installs and repairs electrical wiring and components in and around residential buildings. For more information you can

    call us - +968-95031616

    ReplyDelete

Popular Posts